Hello everyone and welcome All. current chapter is number 11 and topic is going online with

2

00:00:10,240  -->  00:00:16,384
real Hardware I wanted to just show

3

00:00:16,640  -->  00:00:22,784
about the diagnostic LEDs after power on and how do we connect with

4

00:00:23,040  -->  00:00:29,184
ethernet cable to real simotion drive based CPU and let's get started

5

00:00:33,792  -->  00:00:39,936
So I opened my last project as an example

6

00:00:41,472  -->  00:00:47,616
First of all I've connected with the phonecam and you can see

7

00:00:47,872  -->  00:00:54,016
Situation of my drive first of all I just want to power on

8

00:00:57,856  -->  00:01:04,000
So as you

9

00:01:04,256  -->  00:01:09,120
You can hear the sound of the fan

10

00:01:09,376  -->  00:01:12,192
Is testing during power on

11

00:01:12,448  -->  00:01:15,008
no you see the diagnostic lights

12

00:01:15,264  -->  00:01:19,872
The CF card with some firmware version is inserted

13

00:01:20,128  -->  00:01:22,432
in our CPU

14

00:01:23,456  -->  00:01:29,600
As you know there's a seven segment display in your commissioning and maintenance manual

15

00:01:29,856  -->  00:01:35,744
You can examine more details about the what's the meaning of the

16

00:01:36,000  -->  00:01:37,280
codes

17

00:01:37,536  -->  00:01:43,680
If there's something wrong during the start-up phase than you stuck in some

18

00:01:43,936  -->  00:01:49,056
other point 6 means the system is started

19

00:01:50,592  -->  00:01:56,736
our CPU is ready to download and operate all the communication ports are available

20

00:01:56,992  -->  00:02:03,136
So it's our case if you see the number 8 that means at fault on fan module

21

00:02:05,440  -->  00:02:06,720
So now

22

00:02:06,976  -->  00:02:13,120
As I can see the ready state it's blinking red led that means

23

00:02:13,376  -->  00:02:16,704
Is there is an error on the sinamics side

24

00:02:16,960  -->  00:02:21,824
And CPU is set in run mode or use a program is running

25

00:02:22,080  -->  00:02:28,224
And the system fault red light blinks so there's a group failure that means

26

00:02:28,480  -->  00:02:30,272
for the profinet

27

00:02:31,040  -->  00:02:37,184
there are some device or models are configured but not available or there is an error on the

28

00:02:37,440  -->  00:02:38,208
profinet network

29

00:02:38,976  -->  00:02:42,816
Let's try to reset or CPU

30

00:02:46,400  -->  00:02:52,544
as you see it's a similar way

31

00:02:52,800  -->  00:02:56,896
Power off and on again this is a software

32

00:02:57,152  -->  00:03:03,296
power on similar with reset button you can do it via webserver

33

00:03:04,832  -->  00:03:10,464
Download information from the web server CPU itself

34

00:03:10,720  -->  00:03:12,768
Restarting the system

35

00:03:14,048  -->  00:03:20,192
So as we mentioned.

36

00:03:20,448  -->  00:03:26,592
double Fan and battery module is a must in our new CPUs I just connected my

37

00:03:26,848  -->  00:03:28,128
ethernet cable

38

00:03:30,176  -->  00:03:31,456
on service port

39

00:03:31,968  -->  00:03:34,272
X127

40

00:03:36,064  -->  00:03:42,208
So let's say what will be happen when you hit the diagnostic button

41

00:03:48,608  -->  00:03:52,704
you see stop and

42

00:03:53,216  -->  00:03:57,056
SU let's are blinking

43

00:03:57,312  -->  00:03:59,104
SU LED are orange color

44

00:04:03,968  -->  00:04:07,552
It's like going to 2 hz for current

45

00:04:11,136  -->  00:04:16,768
After the creating a diagnostic files in your CF card is finished

46

00:04:17,024  -->  00:04:20,863
Once you see it the lights are

47

00:04:21,119  -->  00:04:26,239
Lights off again and you're RUN LED is

48

00:04:26,751  -->  00:04:29,823
Green standstill again

49

00:04:30,079  -->  00:04:36,223
And how do we use our simotion NCK NC Kernel service switch or

50

00:04:36,479  -->  00:04:39,807
Let's give it a try

51

00:04:40,575  -->  00:04:43,903
I would rotate know as default

52

00:04:44,159  -->  00:04:47,999
The positions are 0 and 0

53

00:04:55,423  -->  00:04:57,727
I just rotated for once

54

00:04:59,263  -->  00:05:02,079
That's your see the CPU is goes

55

00:05:02,335  -->  00:05:03,615
 to STOPU mode

56

00:05:04,127  -->  00:05:05,663
let's Try again

57

00:05:14,879  -->  00:05:16,927
I'll just write it in twice

58

00:05:18,463  -->  00:05:20,255
And 

59

00:05:20,511  -->  00:05:22,303
it is in stop mode

60

00:05:23,327  -->  00:05:26,655
With the PLC switch at 2

61

00:05:29,215  -->  00:05:33,055
For the memory reset you have to go to switch mode 3

62

00:05:38,687  -->  00:05:42,271
then you see the light blinks

63

00:05:44,063  -->  00:05:46,879
Both of you go back and try again

64

00:05:49,439  -->  00:05:55,071
You'll see it's in stop mode by the way if you rotate and switch

65

00:05:55,583  -->  00:05:58,911
You'll see the current state of your switch

66

00:05:59,935  -->  00:06:01,215
and now

67

00:06:03,007  -->  00:06:08,639
The system is executing the memory reset function

68

00:06:09,663  -->  00:06:13,759
and After that system will be restarted

69

00:06:15,039  -->  00:06:17,855
How to do factory reset function?

70

00:06:18,623  -->  00:06:20,159
You have to

71

00:06:21,439  -->  00:06:26,047
Make your service switch to State 1 and your PLC switch

72

00:06:26,303  -->  00:06:32,447
Position set the 3 after that you can hit here with reset button or switch

73

00:06:32,703  -->  00:06:38,847
 the power off your simotion

74

00:06:40,127  -->  00:06:42,431
will be Execute and factory reset

75

00:06:43,711  -->  00:06:45,759
So it just case

76

00:06:46,015  -->  00:06:52,159
PLC memory reset is executed and the retain variables and

77

00:06:52,415  -->  00:06:55,743
The other Global variables are initialized

78

00:06:57,023  -->  00:07:00,351
But at this case the hardware is consist not deleted

79

00:07:00,607  -->  00:07:05,215
 so let's try with a factory reset

80

00:07:13,663  -->  00:07:16,735
I just set the switch 1 and 3

81

00:07:17,247  -->  00:07:18,527
and:..

82

00:07:18,783  -->  00:07:20,319
I would hit the reset

83

00:07:31,583  -->  00:07:37,727
All of the lights are orange and light on and CPU

84

00:07:38,239  -->  00:07:40,031
is powering on

85

00:07:40,287  -->  00:07:44,127
Then we'll execute factory reset

86

00:07:45,151  -->  00:07:50,271
So the stop Orange LeD is blinking at 1hz

87

00:07:51,551  -->  00:07:55,647
now during start-up phase you see with different numbers

88

00:07:59,743  -->  00:08:01,791
here Afterwards

89

00:08:02,047  -->  00:08:08,191
In your seven segment display if everything's okay and you should see number 6

90

00:08:08,447  -->  00:08:10,751
A red dot light blinking

91

00:08:11,775  -->  00:08:17,919
So at this time the CPU takes a little bit more because we have executed

92

00:08:18,175  -->  00:08:20,735
Factory reset

93

00:08:20,991  -->  00:08:22,015
So

94

00:08:22,271  -->  00:08:28,415
now it's complete completed you see here the red light and green color blinking

95

00:08:28,671  -->  00:08:34,815
That means sinamicsc sites and factory reset executed

96

00:08:35,071  -->  00:08:36,607
our Program is deleted

97

00:08:36,863  -->  00:08:39,167
So there is no profinet 

98

00:08:39,679  -->  00:08:45,823
Configuration right now and all of the ports of the CPU is reset

99

00:08:46,079  -->  00:08:48,127
The default settings that means

100

00:08:48,383  -->  00:08:54,527
For the IP addresses on Profinet or for the profibus is

101

00:08:54,783  -->  00:09:00,927
The default and let's switch back to 0 and 0

102

00:09:01,183  -->  00:09:02,207
Rotary switch

103

00:09:13,215  -->  00:09:19,359
and now our CPU is in RUN mode there's no problem

104

00:09:19,615  -->  00:09:25,759
I'm running at this case until you see it here there's a system fault red led that means what

105

00:09:26,015  -->  00:09:28,063
The license is missing

106

00:09:35,743  -->  00:09:41,375
Let's try this time I will going to remove the cf card

107

00:09:42,143  -->  00:09:44,447
after power on

108

00:09:45,727  -->  00:09:50,335
You can see the status of the diagnostic lights

109

00:09:52,895  -->  00:09:58,527
I just power off the device and I'm going to remove the card

110

00:10:05,695  -->  00:10:07,743
Let's try

111

00:10:09,535  -->  00:10:15,679
with no memory card

112

00:10:15,935  -->  00:10:22,079
There's no CF card right now and CPU after power on

113

00:10:23,871  -->  00:10:28,735
You'll see here at the diagnostic lights are 3 and 8

114

00:10:32,575  -->  00:10:38,719
And if your file system is defective or there is a Fault In Your CF card

115

00:10:38,975  -->  00:10:45,119
Is defective then you see or CPU couldn't start up

116

00:10:45,375  -->  00:10:49,215
All of the leds are orange

117

00:10:49,471  -->  00:10:54,591
That means there's some fault in or CF cards

118

00:10:54,847  -->  00:10:58,943
Or file system or maybe the CPU itself

119

00:11:23,519  -->  00:11:27,359
Switch on again

120

00:11:28,383  -->  00:11:33,247
Right now I'm going to arrange and set my

121

00:11:35,807  -->  00:11:39,391
And I will set my IP settings

122

00:11:39,903  -->  00:11:42,975
Connect to CPU

123

00:11:51,935  -->  00:11:56,031
Let's go to network status

124

00:11:57,055  -->  00:12:00,383
And check my IP address configuration

125

00:12:02,687  -->  00:12:05,759
Connected to this adapter

126

00:12:06,015  -->  00:12:08,063
Of my pc

127

00:12:10,367  -->  00:12:15,231
So let's try first with the automatic IP configuration

128

00:12:15,487  -->  00:12:19,583
i will go in the simotion side

129

00:12:22,399  -->  00:12:25,983
And I will try to find the accessible nodes

130

00:12:29,823  -->  00:12:33,151
So here you see

131

00:12:35,199  -->  00:12:36,479
our device

132

00:12:37,247  -->  00:12:40,319
IP address and the firmware version

133

00:12:40,575  -->  00:12:43,135
with CPU type

134

00:12:43,391  -->  00:12:47,743
So there are some files as diagnostics regenerated

135

00:12:48,255  -->  00:12:53,375
A couple of minutes ago this is the default

136

00:12:53,631  -->  00:12:55,167
Profibus address

137

00:12:55,423  -->  00:12:56,191
So

138

00:12:57,727  -->  00:13:03,871
Before I go to online to device I have to check my CPU type and

139

00:13:04,895  -->  00:13:11,039
CPU type on firmware must be matched to go online with the real device so

140

00:13:12,063  -->  00:13:18,207
I'm going on my Hardware I will open the hardware configuration and I will replace my CPU type

141

00:13:21,279  -->  00:13:23,327
It's replace objects

142

00:13:25,119  -->  00:13:28,703
D445-2with firmaware 5.3

143

00:13:31,007  -->  00:13:33,311
save compile

144

00:13:35,103  -->  00:13:35,871
So

145

00:13:36,639  -->  00:13:42,783
At this case there is no project backup because I couldn't see any compressor

146

00:13:43,039  -->  00:13:44,575
Zip files

147

00:13:46,879  -->  00:13:51,743
I change the type of CPU that's why cout will upgrades

148

00:13:52,767  -->  00:13:54,815
The items in my

149

00:13:55,071  -->  00:13:58,399
Project so I need the close

150

00:13:58,911  -->  00:14:01,983
The openned step 7 applications first

151

00:14:02,751  -->  00:14:06,079
And afterwards

152

00:14:07,103  -->  00:14:11,455
Because the all of the other services and applications

153

00:14:12,735  -->  00:14:14,527
Shouldn't be used

154

00:14:15,551  -->  00:14:18,367
During this upgrade procedure

155

00:14:23,231  -->  00:14:27,327
In my projects simotion Scouts

156

00:14:27,583  -->  00:14:33,727
will Change the templates on upgrade the firmware of the current components both

157

00:14:33,983  -->  00:14:38,079
And simotion side and sinamics side

158

00:14:38,335  -->  00:14:44,479
So that means program structure or hardware and software

159

00:14:44,991  -->  00:14:51,135
That's why I have to close the openned programs for step seven

160

00:14:51,391  -->  00:14:56,767
hardware Configuration so on

161

00:14:59,327  -->  00:15:02,911
after that i can hit here to set button

162

00:15:08,031  -->  00:15:09,055
It's closes

163

00:15:09,311  -->  00:15:12,127
By automatically

164

00:15:12,639  -->  00:15:16,479
Begin to update procedure

165

00:15:46,175  -->  00:15:50,271
i hit yes

166

00:15:53,599  -->  00:15:57,183
Exiting step7 application

167

00:16:11,263  -->  00:16:15,359
So it is updating to sinamics side projects closed

168

00:16:17,151  -->  00:16:18,943
Now reopens

169

00:16:19,455  -->  00:16:24,319
You can trace the open window for changing device procedure

170

00:16:27,903  -->  00:16:33,791
And that's it I have to save and compile project

171

00:16:39,423  -->  00:16:45,311
So here you see some error messages about related to libraries

172

00:16:45,567  -->  00:16:48,639
Your library should support

173

00:16:49,663  -->  00:16:50,687
Related

174

00:16:50,943  -->  00:16:52,479
Device version

175

00:16:56,319  -->  00:17:01,951
It was with TP CAM

176

00:17:02,207  -->  00:17:08,351
I should select TP CAM

177

00:17:14,495  -->  00:17:17,567
for this one.

178

00:17:24,735  -->  00:17:28,575
I must arrange the libraries first

179

00:17:29,343  -->  00:17:33,695
for LMCbasic is required to TP

180

00:17:35,487  -->  00:17:39,839
With current CPU version and

181

00:17:40,095  -->  00:17:41,631
Technology package

182

00:17:43,679  -->  00:17:45,727
Modular machines

183

00:17:46,751  -->  00:17:49,567
Let's say d445

184

00:17:50,847  -->  00:17:52,895
Tp cam

185

00:17:55,199  -->  00:17:59,039
Message related with the last Library

186

00:18:00,063  -->  00:18:01,855
tp cam

187

00:18:04,159  -->  00:18:05,951
Okay

188

00:18:06,463  -->  00:18:09,279
First I should try to compile libraries

189

00:18:13,887  -->  00:18:16,447
i can save and compile the project

190

00:18:22,847  -->  00:18:28,991
Source code and program project is compiled for the new type CPU

191

00:18:30,783  -->  00:18:32,063
It's

192

00:18:32,319  -->  00:18:33,855
Constant

193

00:18:34,879  -->  00:18:38,207
Let's try to hit the go online button

194

00:18:42,559  -->  00:18:48,703
connected to cpu side let's try to connect to sinamics sides

195

00:18:49,727  -->  00:18:55,871
So if this case the subnet mask for the profibus integrity

196

00:18:56,127  -->  00:19:02,271
Between integrated and Simotion should be same as online

197

00:19:02,527  -->  00:19:08,671
And offline otherwise when it's different you're not an able to or not

198

00:19:08,927  -->  00:19:11,999
Able to go online sinamics sites

199

00:19:12,511  -->  00:19:18,655
After you download the hardware it will be changed according to project

200

00:19:18,911  -->  00:19:19,935
Settings

201

00:19:20,191  -->  00:19:22,751
So that are 2 ways

202

00:19:23,519  -->  00:19:29,407
You might follow you can just download your project or you can

203

00:19:30,175  -->  00:19:31,967
hit here

204

00:19:32,223  -->  00:19:34,527
Search accessible notes

205

00:19:34,783  -->  00:19:40,927
You will see the subnet ID of the sinamics integrated

206

00:19:41,439  -->  00:19:47,583
You can copy and paste in your project it's also all the way to do to go online with

207

00:19:47,839  -->  00:19:49,631
Sinamics integrated

208

00:19:50,655  -->  00:19:56,799
You sure are facing with some problems

209

00:19:57,311  -->  00:19:59,359
Maybe

210

00:19:59,871  -->  00:20:01,151
At this case

211

00:20:01,407  -->  00:20:02,943
You

212

00:20:03,711  -->  00:20:09,855
couldn't route that means you're PG PC interface is assigned

213

00:20:10,111  -->  00:20:11,135
Wrong

214

00:20:11,647  -->  00:20:13,183
As you can see here

215

00:20:14,463  -->  00:20:18,303
You should change the assignment

216

00:20:20,095  -->  00:20:22,399
ethernet all I P address

217

00:20:22,655  -->  00:20:28,799
Correct than you should assign to your ethernet adapter

218

00:20:29,567  -->  00:20:32,895
Click online axis to active

219

00:20:33,919  -->  00:20:35,711
So let's update

220

00:20:41,087  -->  00:20:43,647
it is searching again

221

00:20:48,767  -->  00:20:54,911
All of the other components in your network like other CPUs

222

00:20:55,167  -->  00:20:56,703
HMIs

223

00:20:57,727  -->  00:20:59,007
and models

224

00:20:59,775  -->  00:21:02,591
You're going to list here

225

00:21:04,383  -->  00:21:09,759
So it just lets right click and change the properties of the CPU

226

00:21:12,063  -->  00:21:18,208
Okay and it's your case devices selected you should switch to step 7 online

227

00:21:22,816  -->  00:21:26,400
You can also change your settings here

228

00:21:26,912  -->  00:21:29,984
Options to PG PC interface

229

00:21:32,032  -->  00:21:36,640
So right now we are using automatic IP address

230

00:21:38,176  -->  00:21:40,224
let's try update again

231

00:21:43,296  -->  00:21:44,576
and

232

00:21:45,344  -->  00:21:46,880
after that

233

00:21:47,392  -->  00:21:49,440
I'm going to change

234

00:21:49,952  -->  00:21:54,560
give n static IP address to my PC

235

00:21:55,840  -->  00:22:01,472
 will be at the same network

236

00:22:02,496  -->  00:22:07,616
right click properties IP version 4

237

00:22:09,408  -->  00:22:12,736
lets click to ok

238

00:22:12,992  -->  00:22:16,320
And I will hit the update button

239

00:22:21,952  -->  00:22:27,584
And this is the IP address or service port

240

00:22:35,776  -->  00:22:39,360
The situation is the same

241

00:22:40,384  -->  00:22:42,176
So let's

242

00:22:42,688  -->  00:22:48,832
Right-click open Hardware configuration and first project download CPU

243

00:22:50,624  -->  00:22:53,952
You see here

244

00:22:55,488  -->  00:23:01,632
the Profibus integrated subnet ID mask according to our project right now

245

00:23:01,888  -->  00:23:05,472
right now current state of our CPU is as Factory

246

00:23:05,728  -->  00:23:11,104
That's why we couldn't see any subnet ID on the CPU

247

00:23:12,640  -->  00:23:14,944
So...

248

00:23:15,200  -->  00:23:16,992
Maybe you should see

249

00:23:25,696  -->  00:23:31,840
And I will try to hit the okay button and CPU goes to stop mode

250

00:23:32,864  -->  00:23:36,448
Well I have downloaded the hardware and

251

00:23:37,728  -->  00:23:42,336
The system will be restarted with software

252

00:23:43,104  -->  00:23:47,456
Restart you see here the current status of the LEDs

253

00:23:47,968  -->  00:23:52,320
Depends on your CPU type

254

00:23:52,576  -->  00:23:58,720
It's may take couple of minutes

255

00:23:58,976  -->  00:24:02,816
Yes so you hear the fan voice

256

00:24:03,328  -->  00:24:09,472
My system is restarted now I can go to my project and

257

00:24:10,240  -->  00:24:11,776
Refresh the

258

00:24:12,032  -->  00:24:14,080
Network for

259

00:24:14,336  -->  00:24:16,896
Searching accessible nodes

260

00:24:28,672  -->  00:24:34,816
And right now I see the subnet ID downloaded from my project let's go

261

00:24:36,608  -->  00:24:38,656
Select the target devices

262

00:24:38,912  -->  00:24:40,960
CPU on sinamics

263

00:24:41,984  -->  00:24:45,824
When I hit the connect online button

264

00:24:47,104  -->  00:24:50,432
Now I'm online to my CPU

265

00:24:50,688  -->  00:24:56,832
You see here the difference between online and offline partner so

266

00:24:57,088  -->  00:25:00,416
Let's select and download the sinamics side first

267

00:25:24,224  -->  00:25:27,040
 download the sinamics side first

268

00:25:27,296  -->  00:25:33,184
The first LED ready is related with the sinamics integrated only

269

00:25:33,696  -->  00:25:36,256
So you see here the orange button

270

00:25:37,280  -->  00:25:38,304
That means

271

00:25:39,840  -->  00:25:42,144
It's downloading Project

272

00:25:48,032  -->  00:25:54,176
So after that red light blinks that means there are some alarms in your sinamics side

273

00:25:55,456  -->  00:26:00,064
I will go and openin our topology

274

00:26:00,320  -->  00:26:01,088
It's

275

00:26:01,600  -->  00:26:04,416
now

276

00:26:04,928  -->  00:26:08,256
you see here we have configured

277

00:26:08,512  -->  00:26:14,656
some Components in our automation project set but actually there's no components in our

278

00:26:14,912  -->  00:26:16,192
Control unit

279

00:26:16,704  -->  00:26:21,824
but we have downloaded our projects next thing is copy ram 2 rom

280

00:26:22,080  -->  00:26:24,384
So if you don't do that

281

00:26:24,896  -->  00:26:31,040
After your power off and on you lost the information this time I was selected

282

00:26:31,296  -->  00:26:35,136
siMotion CPU and downloads project

283

00:26:56,128  -->  00:26:59,200
The system will be reset

284

00:27:00,736  -->  00:27:02,272
afterwards

285

00:27:02,784  -->  00:27:08,928
Editor will continue to download our project and

286

00:27:09,184  -->  00:27:10,464
Program data

287

00:27:10,720  -->  00:27:12,256
Technology package

288

00:27:13,024  -->  00:27:14,048
and loaded

289

00:27:14,304  -->  00:27:18,144
TOs loaded first then our programs loaded

290

00:27:20,960  -->  00:27:26,336
As you can see here the CPU is in stop mode

291

00:27:28,640  -->  00:27:34,784
So I can control from here to set CPU the RUN

292

00:27:36,832  -->  00:27:38,624
It's now in RUN STATE

293

00:27:40,160  -->  00:27:45,024
there is a last thing That I want to show you about

294

00:27:45,280  -->  00:27:46,816
Real Hardware

295

00:27:47,072  -->  00:27:48,864
with my phone 

296

00:27:49,120  -->  00:27:52,960
 I recorded a short video

297

00:27:53,984  -->  00:27:59,872
with this Video i wanted to show you what will happen

298

00:28:00,128  -->  00:28:05,504
Doing CPU

299

00:28:12,160  -->  00:28:17,024
If you can see CPU is in run mode

300

00:28:20,864  -->  00:28:22,400
that means there is no over Temperature so lets check startup phase

301

00:28:32,384  -->  00:28:38,528
Are you an estimated five minutes for us to temperature rises up then get the failure

302

00:28:47,744  -->  00:28:51,584
and after switch on at this case you see here

303

00:28:51,840  -->  00:28:54,656
All of the oranged LED

304

00:29:04,640  -->  00:29:10,784
you see 7 segment are number 8 red dot doesn't blink. That means fan battery failure.

305

00:29:24,864  -->  00:29:28,960
So let's start with the old temperature...

306

00:29:31,776  -->  00:29:33,824
Basiccaly that's it

307

00:29:36,128  -->  00:29:39,200
After the power on

308

00:29:39,456  -->  00:29:44,832
CPU Just checking system and if there is a need to run the fan for cooling

309

00:29:45,856  -->  00:29:52,000
When the temperature rises over 45 degrees for instance.

310

00:29:52,256  -->  00:29:56,864
Try to run the fan at this case you're got the failure

311

00:29:58,656  -->  00:30:01,728
You'll see CPU set to stop mode

312

00:30:02,496  -->  00:30:05,824
Return alarm on 7 segment display 8

313

00:30:07,872  -->  00:30:12,224
This is the last thing related to this topic

314

00:30:14,784  -->  00:30:20,928
So unfortunately these days I'm sorry I couldn't show you

315

00:30:21,184  -->  00:30:27,328
Any drive or motor in Real Hardware rotate motor due to CORONA DAYS

316

00:30:28,608  -->  00:30:30,912
It is risky to go outside

317

00:30:31,424  -->  00:30:32,960
So

318

00:30:33,216  -->  00:30:36,544
in my house

319

00:30:37,056  -->  00:30:38,336
there is only CPU

320

00:30:38,592  -->  00:30:44,224
But you're able to walk and run your programs with simosim simulation

321

00:30:55,744  -->  00:30:59,328
That's it for this chapter and see you next time